Smart Water Pump Controller (Single-phase / Three-phase, One-Control-One & One-Control-Two)
Application Scope: Suitable for high-rise water supply, underground sewage drainage, and deep well pumping systems.
Main Features: • Supports one-in-use / one-on-standby mode, dual-pump alternation, and dual-pump simultaneous start at ultra-high water level. • Real-time display of voltage, current, and water levels (upper & lower tanks). • Manual/Automatic switchable control with one button. • Fault cause display with audible and visual alarms. • Supports upper tank filling, lower tank drainage, and constant pressure water supply. • Comprehensive protection: dry-run, overload, locked rotor, phase loss, short circuit, over/under voltage. • Automatic restart after voltage returns to normal. • One-key setup for overload and dry-run protection. • Manual/Auto start-stop; Timed start-stop; Power-on auto restart. • Level/Pressure control; direct switching between control modes. • Displays contact status of electric pressure gauge (upper/lower limit).
Technical Specifications: • Rated Voltage: AC 380V ±10%, 50Hz • Motor Power: 0.75 kW – 15 kW • Static Power Consumption: < 3W • Water Level Indication: 3 levels (upper/lower tank) • Anti-rust inspection cycle: 0–30 days (adjustable) • Timed Start/Stop: 0–990 min (adjustable) • No-load Restart Delay: 0–990 min (adjustable) • Over/Under Voltage Protection Range: 304V–456V (trip ≤3s; adjustable) • Over/Under Current Trip Delay: 0.1s – 3 min (inverse-time) • Phase Loss Trip Time: < 2 seconds